ファクトリーオートメーション(FA)
プロセスオートメーション(PA)
Not available for purchase
Not available for purchase

Solenoid Driver KCD0-SD-Ex1.1245

KCD0-SD-Ex1.1245
  • 1-channel isolated barrier
  • 24 V DC supply (loop powered)
  • Current limit 45 mA at 12 V DC
  • Housing width 12.5 mm
  • Up to SIL 3 acc. to IEC/EN 61508

注: Pepperl+Fuchs GmbH(旧社名)で発行された証明書・適合宣言書などすべての製品関連文書は、Pepperl+Fuchs AG(新社名)にそのまま適用されます。

データシート(PDF):


技術データ  KCD0-SD-Ex1.1245

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Rated voltageloop powered
Power dissipation< 1 W
Input
Connection sidecontrol side
Connectionterminals 5, 6
Rated voltage19 ... 30 V DC
Current≤ 72 mA at Ui = 19 V, ≤ 50 mA at Ui = 30 V with 265 Ω output load
≤ 45 mA at Ui = 19 V, ≤ 31 mA at Ui = 30 V with shorted output
≤ 14 mA at Ui = 19 V, ≤ 11 mA at Ui = 30 V no load at output
Inrush current≤ 200 mA after 100 µs
Output
Connection sidefield side
Connectionterminals 1+, 2-
Internal resistor≤ 238 Ω
Current≤ 45 mA
Voltage≥ 12 V
Open loop voltage≥ 22.7 V
Output current45 mA
Output signalThese values are valid for the rated operating voltage 19 ... 30 V DC.
Energized/De-energized delaysingle operation: typ. 1.7 ms/50 µs; periodical: typ. 5 µs/50 µs
Galvanic isolation
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Protection against electrical shockUL 61010-1
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Height119 mm
Width12.5 mm
Depth114 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 06 ATEX 0170
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC , Ex-Hexagon II (1)D [Ex ia Da] IIIC , Ex-Hexagon I (M1) [Ex ia Ma] I
Output[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage25.2 V
Current110 mA
Power693 mW
Input
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificatePF 06 CERT 0971 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0419 (cFMus)
UL approval
Control drawing116-0420 (cULus)
IECEx approval
IECEx certificateIECEx BAS 06.0032
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: KCD0-SD-Ex1.1245

Informative Literature: KCD0-SD-Ex1.1245

Language Selection:
Literature言語ファイルタイプファイルサイズ
Application Report - Energy Generation in Wastwater Treatment PlantsENGPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenENGPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsENGPDF526 KB

Product Documentation: KCD0-SD-Ex1.1245

Language Selection:
Product information言語ファイルタイプファイルサイズ
Application Guideline Solenoid DriversENGPDF734 KB
Safety and Security Documentation
Instruction manualENGPDF168 KB
Safety ManualENGPDF414 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KCD0-SD-Ex1.1245

Language Selection:
CAD言語ファイルタイプファイルサイズ
CAD 3-D / CAD 3-DALLSTP3086 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ42 KB

Approvals: KCD0-SD-Ex1.1245

Language Selection:
Certificates認証番号言語ファイルタイプファイルサイズ
Australia SIMTARS Group IANZEx 08.2007XALLPDF295 KB
Baseefa IECEx Certificate of ConformityIECEx BAS 06.0032ALLLINK---
Canada FMFM18CA0116XALLPDF2690 KB
Canada UL cULE106378 cUL (QUZW7)ALLLINK---
China SITIIAS CCC Ex Certificate2020322316001222 (Singapore)ALLPDF1036 KB
DNV MarineTAA00001WXALLPDF114 KB
Europe Baseefa ATEX Category (M1) ATEX Category (1) GDBaseefa 06 ATEX 0170ALLPDF679 KB
Europe Pepperl+Fuchs ATEX Category 3 GPF06CERT0971XALLPDF195 KB
India PESO (India) CCOEA/P/HQ/KA/104/6090 (P577495)ALLPDF125 KB
Korea KOSHA [Ex ia]17-AV4BO-0294ALLPDF457 KB
South Africa MASCMASC MS/17-0857ALLPDF216 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20170501 - E106378 RepRef 20081022ALLPDF244 KB
USA FMFM19US0117XALLPDF2447 KB
USA ULE106378 UL (QUZW)ALLLINK---
exida Functional Safety AssessmentP+F 1109-099-C R028 V1R0ALLPDF380 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF209 KB
Control drawing FM / Control drawing FM   ALLPDF208 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0026BALLPDF54 KB

関連製品: KCD0-SD-Ex1.1245

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
2-pin screw terminal, For KC modules of K-System, Packaging unit: 5 pieces greenpa
2-pin screw terminal, For KC modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.